BRAND | ProMinent |
Product | 792920 |
Description | Sensor |
Internal code | IMP4424826 |
Custom code | 90278020 |
Technical specification | CLE 3 ma-2ppm Sensor for measuring free chlorine in clear water applications include applications in drinking water and swimming pool Measurement variable: free chlorine Measuring range: 0.02... 2.0 mg/l Reference method: DPD1 pH range: 5.5... 8.0 temperature: 5... 45°C max. pressure: 1.0 bar inflow: 30... 60 l/h (in bypass, open outlet of measuring water) Output signal: 4... 20 mA ~ temperature compensated, uncalibrated, no galvanic isolation Sensor fitting: DGM DLG measuring principle: amperometric, 2 electrodes, membrane covered Installation in bypass to process water pipe Connection to controller via control cable LiyY 2x0.25 qmm order number (test lead not included) |
Please send us your request per e-mail, so we can send you our offer with competitive prices and delivery time for ProMinent - 792920 Sensor number or any other model you need. We can offer competitive price, and delivery time with wide products distribution network in Germany Industrial products Market.
WE SELL ONLY NEW AND ORIGINAL PRODUCTS!
metering pump
Universal cable
Spare parts set 1602-2 PVT
magnetic dosing pump
Pulsation dampener
LEVEL SWITCH
PUMP MEMBRANE
PUMP MEMBRANE
magnetic dosing pump
magnetic dosing pump